    Solar Power for Remote Monitoring...Made Simple


    Solar Power for SCADA Remote ApplicationsSolar Power for Remote Monitoring has never been easier with TESSCO's new in stock solar power solutions. These pre-sized systems are easy to order and ship directly to your site. Simply connect your Raven X, MDS or Phoenix Contact Radio and you are ready to go.

    Instantly select your Remote Monitoring solar power system...today!
    • Guaranteed to work with GE-MDS, Raven X and Phoenix Contact radio equipment
    • Complete, turn-key solar power systems ship within days of your order, not weeks
    • Systems are Class 1 Div 2 Approved
    • 4 New enclosure sizes to choose from for radio and radio + RTU ready installations
    • DIN rail platform means easy click-in equipment installation

    The solar map and chart below will help you determine which solar system is right for you.

    In-Stock Solar System Sizing Matrix

    Enclosure: Fiberglass 12x10x6

    Maximum Daily Loads (Amp / Hr / Day)
      Zone A Zone B Zone C Zone D Zone E
    10W/12VDC/18AmpHr 2.48 2.03 1.58 1.13 0.68
    20W/12VDC/18AmpHr 4.95 4.05 3.15 2.25 1.35
    40W/12VDC/18AmpHr 10.23 8.37 6.51 4.65 2.79
    20W/12VDC/36AmpHr 4.95 4.05 3.15 2.25 1.35
    40W/12VDC/36AmpHr 10.23 8.37 6.51 4.65 2.79

    Enclosure: Aluminum 18x16x12

    Maximum Daily Loads (Amp / Hr / Day)
      Zone A Zone B Zone C Zone D Zone E
    10W/12VDC/36AmpHr 2.48 2.03 1.58 1.13 0.68
    20W/12VDC/36AmpHr 4.95 4.05 3.15 2.25 1.35
    40W/12VDC/36AmpHr 10.23 8.37 6.51 4.65 2.79

    Enclosure: Aluminum 26x16x12

    Maximum Daily Loads (Amp / Hr / Day)
      Zone A Zone B Zone C Zone D Zone E
    40W/12VDC/99AmpHr 10.23 8.37 6.51 4.65 2.79
    50W/12VDC/99AmpHr 12.83 10.50 8.16 5.83 3.50
    65W/12VDC/99AmpHr 15.47 12.66 9.84 7.03 4.22
    85W/12VDC/99AmpHr 20.71 16.94 13.18 9.41 5.65
    130W/12VDC/99AmpHr 30.48 24.94 19.40 13.86 8.31

    Enclosure: Aluminum 26x27x12

    Maximum Daily Loads (Amp / Hr / Day)
      Zone A Zone B Zone C Zone D Zone E
    85W/12VDC/198AmpHr 20.71 16.94 13.18 9.41 5.65
    130W/12VDC/198AmpHr 30.48 24.94 19.40 13.86 8.31

     HOW TO
    Calculate Your Equipment's Daily Load

    Equipment Power Draw given in DC Amps

    1.25 Amp continous (24 hours/day) load at 12 Volts DC (VDC)

    DC Voltage 12VDC
    Listed Equipment Power Draw 1.25 Amps
    Duty Cycle 24 Hours

    1.25 X 24 = 30 amp-hours per day (Ah/day) @ 12VDC

    Equipment Power Draw given in Watts

    50 Watts continous (24 hours/day) load at 12 Volts DC (VDC)

    Equipment Wattage Draw  50 Watts 
    Duty Cycle  24 Hours 
    50 X 24 = 1200 watt-hours (wh/day)

    Watt Hours Per Day (wh/day) 1200 wh/day
    Desired System Voltage 12VDC
    1200 wh/day /12VDC = 100 amp-hours per day (Ah/day) @ 12VDC

    Your Total SourceFor more information contact TESSCO
    at 800-472-7373 or email us today.

    Back to Top